Universal Loadbreak Cutout Cover CT-D04
-
Compatible with most <27kV loadbreak cutouts, including: ABB, Hubbell-Chance, AlumaForm, MacLean
-
Raptor Claw™ adjustable clip provides a tight, secure fit – no locking pins required
-
Fully covers energized areas and upper cutout sections to reduce wildlife contact and arc flash risk
-
Supports natural self-cleaning of insulator skirts
-
Installs safely via hotstick – no outage or system downtime required
-
Ideal for wildlife protection, system reliability, and live-line work
Install support
Product Intro
Product Description
Protect critical equipment and prevent wildlife-related outages with the Universal Loadbreak Cutout Cover, designed for use on <27kV distribution loadbreak cutouts. The integrated Raptor Claw™ adjustable clip delivers a secure, pin-free fit on most major cutout brands, including ABB, Hubbell-Chance, AlumaForm, and MacLean.
Engineered to fully enclose all energized components and the top portion of the cutout, this innovative cover helps prevent animal contact and flashovers while allowing insulator skirts to self-clean through natural weathering.
With tool-free installation using a hotstick, linemen can install the cover quickly and safely without the need for de-energizing the line, making it ideal for live-line maintenance and rapid reliability improvements.
Additional Information
| Cutout Application | ABB Loadbreak Cutouts, AlumaForm Loadbreak Cutouts, Cooper/Easton Type L Loadbreak Cutouts, Hubbell Chance Type C Loadbreak Cutouts, MacLean Loadbreak Cutouts |
|---|---|
| Flame Retardant Rating | V-0 |
| Hotstick Friendly | Yes |
| Hotstick Installation Tool | No additional tool needed |
| Material | PLS-PP-FR-UV |
| Voltage Rating (up to) | 35 kV |
| Wind Resistance Rating | 120 mph |
|
Tests |
Results |
|
IEEE 1656 / 5.2 Wet Withstand |
>18 kV |
|
IEEE 1656 / 5.3 Wet power frequency flashover |
>95% |
|
IEEE 1656 / 5.4 Lightning Impulse withstand |
125kV |
|
IEEE 1656 / 5.5 Cold temperature test |
Passed / -25C |
|
IEEE 1656 / 5.6 Ultraviolet Aging |
5,000 hours |
|
Wind Retention |
>90 mph |
|
UL 94 Flammability of Plastic Materials |
V-0 |
|
Properties |
Results |
|
ASTM D149 Dielectric strength |
467 V/mil (18.4 kV/mm) |
|
ASTM D2303 Inclined plane tracking and erosion: Initial Tracking (variable voltage) |
4.0 kV |
|
ASTM D638 Tensile Strength @ Yield |
2,400 psi (17 MPa) |
|
ASTM D790 Flexural Modulus |
140,000 psi (966 Mpa) |
|
Regulatory |
ROHS Compliant |
Similar products
You may also like…
-

Universal Medium Equipment & Bushing Cover BC-D02
Add to ListCover for primarily anything larger than a standard transformer bushing, with a shed diameter < 5.5"
-

Universal Small Equipment & Bushing Cover BC-D01
Add to ListCover for most distribution equipment with a shed diameter < 4"
-

Insulating Fusing Tape FTP-200
Add to List2" (5cm) wide self-fusing silicone tape
-

Universal Cutout Cover CT-D02
Add to ListCutout cover most < 27kV porcelain and polymer non-loadbreak cutouts including Chance type C, AlumaForm, ABB,Cooper/Eaton Type L cutouts